| General specifications |
| Signal type |
Analog input |
| Functional safety related parameters |
| Safety Integrity Level (SIL) |
SIL 2 |
| Supply |
| Connection |
Power Rail or terminals 11+, 12- |
| Rated voltage |
19 ... 30 V DC |
| Ripple |
within the supply tolerance |
| Power dissipation |
≤ 1.2 W |
| Power consumption |
≤ 1.6 W |
| Input |
| Connection side |
field side |
| Connection |
terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -) |
| Input resistance |
10 kΩ terminals 4 (common), 6-/2- |
| Output current |
terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F) |
| Transmission range |
-20 ... 0 V |
| Output |
| Connection side |
control side |
| Connection |
terminals 7-, 8+ |
| Voltage |
-20 ... 0 V |
| Load |
≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor) |
| Output resistance |
24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer. |
| Transfer characteristics |
| Cut-off frequency |
10 kHz (-0,1 dB)
20 kHz (-1 dB) |
| Deviation |
DC transfer error (with 10 kΩ load) < 10mV |
| |
After calibration |
additional error with AC superimposed is ±5 mV at 20 °C (68 °F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g.
- square waves (0 ... 20 kHz): 5 Vpp
- sine waves (0 ... 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable. |
| |
Influence of ambient temperature |
(< 100 ppm of span)/K at any point within the span |
| Time delay relative to input |
7.1 ±0.3 µs |
| Ripple |
in 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms |
| Galvanic isolation |
| Output/power supply |
functional insulation, rated insulation voltage 50 V AC |
| Indicators/settings |
| Display elements |
LED |