| Number of digital inputs |
4 |
| Total number of channels (module) |
4 |
| Signal type |
Digital |
| Signal type (voltage) |
24 VDC |
| Sensor connection |
2 x (2-wire, 3-wire); A suitable field side connection module (e.g., 750-614) must also be used to connect other sensors. |
| Input characteristic |
low-side switching |
| Input filter (digital) |
3ms |
| Input current per channel for signal (0) typ. |
7mA |
| Voltage range for signal (0) |
(UV - 5 V) … UV DC |
| Voltage range for signal (1) |
−3 VDC … (UV - 15 V) |
| Input data width (internal) max. |
4Bit |
| Supply voltage (system) |
5 VDC; via data contacts |
| Current consumption (5 V system supply) |
5mA |
| Supply voltage (field) |
24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
| Isolation |
500 V system/field |
| Indicators |
LED (A-D) green: Status DI 1 … DI 4 |
| Number of incoming power jumper contacts |
2 |
| Number of outgoing power jumper contacts |
2 |
| Current carrying capacity (power jumper contacts) |
10A |