Order no. 322-1BL00
Type SM 322
General information
Note -
Features 32 outputs, in groups of 8
DC 24 V
Output current 1 A
SPEED-Bus -
Current consumption/power loss
Current consumption from backplane bus 200 mA
Power loss 6 W
Technical data digital outputs
Number of outputs 32
Cable length, shielded 1000 m
Cable length, unshielded 600 m
Rated load voltage DC 24 V
Current consumption from load voltage L+ (without load) 30 mA
Total current per group, horizontal configuration, 40°C 2.5 A
Total current per group, horizontal configuration, 60°C 2.5 A
Total current per group, vertical configuration 2.5 A
Output current at signal "1", rated value 1 A
Output delay of "0" to "1" 150 µs
Output delay of "1" to "0" 100 µs
Minimum load current -
Lamp load 6 W
Parallel switching of outputs for redundant control of a load possible (only outputs group)
Parallel switching of outputs for increased power not possible
Actuation of digital input
Switching frequency with resistive load max. 1000 Hz
Switching frequency with inductive load max. 0.5 Hz
Switching frequency on lamp load max. 1 Hz
Internal limitation of inductive shut-off voltage L+ (-52 V)
Short-circuit protection of output yes, electronic
Trigger level 1.5 A
Number of operating cycle of relay outputs -
Switching capacity of contacts -
Output data size 4 Byte
Status information, alarms, diagnostics
Status display green LED per channel
Interrupts no
Process alarm no
www.vipa.com
© by VIPA GmbH, Ohmstr. 4, 91074 Herzogenaurach, Germany
All data with reservation and subject to change.
Publish date: 13.05.2015
Page 2/2
Diagnostic interrupt no
Diagnostic functions no
Diagnostics information read-out none
Supply voltage display green LED per group
Group error display red SF LED
Channel error display none
Isolation
Between channels
Between channels of groups to 8
Between channels and backplane bus
Insulation tested with DC 500 V
Datasizes
Input bytes 0
Output bytes 4
Parameter bytes 0
Diagnostic bytes 0