Детальний опис: M200, джерело живлення 24 В постійного струму, 40 точок введення-виведення, 24 точки введення з 2 загальними клемами, 16 точок транзисторного виходу джерела (0,5 А) з 3 загальними клемами, вбудований 1 послідовний порт типу термінала RS485 + 1 інтерфейс Ethernet
Complementary
| maximum number of I/O expansion module |
4 with 64 discrete output(s) for relay output
4 with 144 discrete output(s) for transistor output |
| supply voltage limits |
20.4…28.8 V |
| inrush current |
35 A |
| voltage state 1 guaranteed |
>= 15 V for input |
| voltage state 0 guaranteed |
<= 5 V for input |
| input impedance |
3.3 kOhm for discrete input |
| response time |
35 µs turn-on, I2...I5 terminal(s) for input
100 µs turn-off, I2...I5 terminal(s) for input
5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input
5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input
35 µs turn-on, I8...I13 terminal(s) for input
100 µs turn-off, I8...I13 terminal(s) for input
55 µs turn-on, I14...I23 terminal(s) for input
125 µs turn-off, I14...I23 terminal(s) for input
1 ms turn-on, Q0...Q15 terminal(s) for output
1 ms turn-off, Q0...Q15 terminal(s) for output |
| configurable filtering time |
0 ms for input
3 ms for input
12 ms for input |
| maximum current per output common |
2 A at COM 0
2 A at COM 1
4 A at COM 2 |
| output frequency |
100 kHz for fast output (PWM/PLS mode) at Q0...Q1 |
| maximum leakage current |
0.1 mA for transistor output |
| maximum voltage drop |
<1 V |
| maximum tungsten load |
<12 W for output and fast output |
| protection type |
Overload and short-circuit protection at 2 A |
| reset time |
1 s automatic reset |
| memory capacity |
512 byte internal flash for backup of programs |
| data storage equipment |
32 GB micro SD card (optional) |
| battery type |
BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s) |
| backup time |
3 years at 25 °C (by interruption of power supply) |
| execution time for 1 KInstruction |
0.3 ms for event and periodic task |
| execution time per instruction |
0.2 µs Boolean |
| exct time for event task |
60 µs response time |
| clock drift |
<= 90 s/month at 25 °C |
| regulation loop |
Adjustable PID regulator up to 14 simultaneous loops |
| positioning functions |
PWM/PLS 2 channel(s) at 100 kHz |
| control signal type |
Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode)
Pulse/direction at 100 kHz for fast input (HSC mode)
Single phase at 100 kHz for fast input (HSC mode)
CW/CCW at 100 kHz for fast input (HSC mode) |
| counting input number |
4 fast input (HSC mode) at 100 kHz 32 bits |
| integrated connection type |
USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with terminal block connector and RS485 interface
Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface
Isolated serial link serial 2 with terminal block connector and RS485 interface |
| transmission rate |
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
12 Mbit/s for USB |
| communication port protocol |
USB port: USB - SoMachine-Network
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network |
| local signalling |
1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED per channel (green) for I/O state |
| electrical connection |
Mini B USB 2.0 connectorfor a programming terminal
removable screw terminal blockfor inputs
removable screw terminal blockfor outputs
removable screw terminal block, 3 terminal(s) for connecting the 24 V DC power supply
removable screw terminal block, 4 terminal(s) for connecting the serial link1 |
| maximum cable distance between devices |
Unshielded cable: <50 m for input
Shielded cable: <10 m for fast input
Shielded cable: <10 m for high speed input
Unshielded cable: <150 m for output |
| insulation |
Non-insulated between inputs
Between input and internal logic at 500 V AC
Between fast input and internal logic at 500 V AC
Between input groups at 500 V AC
Between output and internal logic at 500 V AC
Between output groups at 500 V AC
Between supply and internal logic at 500 V DC |
| marking |
CE |
| mounting support |
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715 |
| height |
90 mm |
| depth |
70 mm |
| width |
175 mm |
| net weight |
0.522 kg |
Environment
| IP degree of protection |
IP20 with protective cover in place |
| standards |
EN/IEC 61131-2
EN/IEC 61010-2-201 |
| electromagnetic compatibility |
Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz...3 GHz) conforming to EN/IEC 61000-4-3
Magnetic field at power frequency - test level: 30 A/m conforming to EN/IEC 61000-4-8
Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (serial link) conforming to EN/IEC 61000-4-4
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (power lines (AC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (relay output) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (shielded cable) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 0.5 kV (power lines (DC)) conforming to EN/IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (AC)) conforming to EN/IEC 61000-4-5
Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to EN/IEC 55011
Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to EN/IEC 55011
Radiated emission - test level: 40 dBμV/m QP class A (10 m) conforming to EN/IEC 55011
Radiated emission - test level: 47 dBμV/m QP class A (10 m) conforming to EN/IEC 55011 |
| shock resistance |
15 gn for 11 ms
30 gn for 6 ms |
| immunity to microbreaks |
2 ms |
| vibration resistance |
3.5 mm at 5…8.4 Hz on symmetrical rail
1 gn at 8.4…150 Hz on symmetrical rail
3.5 mm at 5…8.7 Hz on panel mounting
2 gn at 8.7…150 Hz on panel mounting |
| relative humidity |
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage) |
| ambient air temperature for operation |
0…55 °C (horizontal installation) |
| ambient air temperature for storage |
-25…70 °C |
| pollution degree |
<= 2 |
| operating altitude |
0...2000 m |
| storage altitude |
0…3000 m |