CP-2080 LTE - CPU, 2x ETH, 4 DI, 6 RO, 2 DO, CIB, LCD
CP-2080 LTE - CPU, 2x ETH, 4 DI, 6 RO, 2 DO, CIB, LCD
Характеристики та опис

Основні

ВиробникTeco
Країна виробникЧехія
СтанНовий

Користувальницькі характеристики

DI4x DI/HSC
DO2x DO 6x RO
COM2x ETH 10/100 4x Serial channel (2x free slot) 1x USB device 1x USB host 1x TCL2 master 1x CIB master
The CP-2080 is a second-generation Foxtrot basic module, with a central unit and an integrated combination of a total of 12 digital inputs and outputs in a compact size occupying a width of 6 modules on a DIN rail. It is thus possible to have a variant with a built-in LTE modem for direct connection to the Internet via a mobile operator. Of course, there are masters of both system expansion buses - TCL2 (up to 10 addressable modules) and two-wire CIB Common Installation Bus® (up to 32 addressable modules). It can therefore be extended in the same way as other basic modules. It is equipped with a total of 12 I / Os:     four galvanically separated digital inputs     two semiconductor digital outputs     six relay outputs organized into two groups of three with their own common terminal Communication capabilities of the basic module CP-2080:     2x Ethernet interface 100 Mbit / s, each with up to 32 simultaneous connections (programming and general IP communication)     USB micro (programming)     USB A for Flas memory, WiFi adapter (client and AP - Access point) etc.     Variant with built-in LTE modem for direct wireless connection to the Internet via a mobile network operator     Slots for up to 4 optional serial interfaces RS-485, RS-232 24 V DC power supply, possibility of direct connection of a backup battery for uninterrupted operation in case of 230 V AC mains failures. CP-2080 is equipped with a new powerful central unit (CPU series L) with memory     1 MB for user program,     128 MB internal disk for storing files with parallel access from the LAN as a network disk,     16MB fast RAM disk     128/256 kB Datalobox     microSD card slot up to 1 TB     File management is provided by a journaling file system     Local communication with the user via OLED display (4 lines / graphic) and 6-key keyboard
DI4x DI/HSC
DI/AI
DO2x DO
6x RO
AI
AO
COM2x ETH 10/100
4x Serial channel (2x free slot)
1x USB Device
1x USB Host
1x TCL2 master
1x CIB master
SENSOR
System parameters of the central unit
Row of central unitI
User program memory1 MB
Memory for user variables / including RETAIN variables320 kB/48 kB
Instruction length4 Byte
Backup of program source code in PLCYes, optional in Mosaic
On-line program change in PLCYes, including I / O configuration change
DataBox - additional internal data memory128/257 kB, optional
File system - Internal Drive in PLC128 MB, journaling file system
File system - RAM disk PLC16 MB
File System - USB Flash DriveSupported
File system - Micro SD cardsupported (except for variants with WLAN1)
Optional memory card slotmicroSD - Card Slot (<= 1TB)
Cycle time per 1k of logic instructions0,036 ms
Cycle time for 1k integer operations0,044 ms
Cycle time for 1k floating point operations0,043 ms
Development environmentMosaic v2018.2 or higher
Programming languagesST, IL, LD, FBD, SFC, CFC
RTC - Real time circuitNo
RTC - Backup timetyp. 500 hours
Integrated Web serverYes
Integrated DataloggerYes
Access to PLC variables via web APIYes
COM - Communication - IP/Ethernet
Ethernet 10/100 Mb (ETHx)2
WLAN1 (internal, optional)1
WLAN2 (external via USB host, optional)1
LTE interface (LTEx, optional)1
Available system modes on ETH and WLANUNI, PC, PLC, PLD
TCP / IP protocolYes
UDP protocolYes
HTTPS protocolYes
HTTP protocolYes
WebSocket protocolYes
Protocol MODBUS/TCPYes
SMTP protocolYes
IEC 60870-5-104 protocolYes
REST APIYes
COM - USB
USB devices interface1x micro-USB
USB host interface1x USB-A
Available system modes on USBPC
COM - Serial channels
max. number of optional serial channels in the basic module4
number of slots for optional submodules with interface (MR-013x)2
max. number of expanding serial channels on the TCL2 bus6
Available system modes on CH5-10UNI, CSJ (CAN)
Modbus RTU / ASCII master protocolYes
Modbus protocol RTU/ASCII slaveYes
Profibus DP master protocol (<180 kbit/s)No
COM - System buses
TCL2 - system I/O bus1x TCL2 master
TCL2 - Range of one branch of the system I/O bus10 I / O modules + 4 operator panels + 6 serial channels
CIB - Common Installation Bus (R): Installation I/O bus1x CIB master (100 mA)
CIB - Address range of one branch of the installation bus32 CFox I/O modules
Power supply
Supply voltage, tolerances24 V DC, +25%, -15%, SELV
Maximum power input10 W
Module thermal/power loss8 W
Internal protectionYes, PTC reversible fuse
CIB branch power supply - parameters of the built-in master1x 100 mA/ 24 V DC
Power supply from ETH, passive PoE - input (appliance)ETH1/Power In
Power supply from ETH, passive PoE - output (source)ETH2 / Power out, jumper configuration
Power supply from ETH, passive PoE - injector parameters24 V DC, 1A
Size and weight
Weight approx.100 g
Product dimensions (width x height x depth)52 x 90 x 62 mm
Module width in multiples of M (17.5 mm)3M
Operating conditions, product standards
Product standardČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical objectII, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989)IP20
Operating areasNormal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installationII, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of deviceModule on DIN rail
Working positionVertical
Type of operation (operating frequency)Continuous
Ambient operating temperatures-20 °C to + 55 °C
Operating temperature maximum (° C)+55°C
Operating temperature minimum (° C)-20°C
Operating relative humidityfrom 10 % up to 95 % without condensation
Operating atmospheric pressuremin. 70 kPa (<3,000 m above sea level)
Storage temperatures–25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / EmissionB, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - noteIn premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunitymin. as required by EN 61131-2: 2007
Sinusoidal vibration endurance10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
DescriptionThe module is packed in a paper box according to the internal packing instructions. The package includes the following documentation. The outer packaging is carried out according to the scope of the order and the method of transport to the transport a package bearing the transport labels and other particulars necessary for transport. Transport from the manufacturer is carried out in the manner agreed upon when ordering. Product transport the customer's own means must be carried out by covered means of transport, in the specified position label on the packaging. The box must be stowed so as to prevent spontaneous movement a damage to the outer packaging. The product must not be exposed to direct weathering during transport and storage influences. Transport is allowed at temperatures from -25 ° C to +70 ° C, relative humidity 10% up to 95% (non-condensing) and a minimum atmospheric pressure of more than 70 kPa. Storage of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly descriptionThe basic module is mounted vertically on the U-rail ČSN EN 50022. The installation of the assembly (basic module and peripheral modules, if applicable) is performed according to TXV 004 50.
Exchangeable submodulesThe optional MR-013x submodules of the serial interface are mounted in the base module CP-2007 on the bottom plate, which is accessible after removing the bottom of the housing. We only handle the module without power supply!
Connection
Connection of power and system communicationconnector with 2.5 mm2 screw terminal
Connection of inputs / outputsconnector with screw terminal 2.5 mm2
EthernetRJ-45
Serial channelsscrew-type connector 9x 1.5 mm2
USB device connectiontype micro B
USB host connectiontype A
Module operation
Module configurationThe module is operated, set and diagnosed from the MOSAIC programming environment. It is also possible to connect to the PLC using a web browser on port 8080. If the PLC has an IP address set eg 192.168.134.178 (default address on port ETH1, port ETH2 has DHCP enabled), just enter the address in the form http://192.168.134.178:8080 and the web browser displays the PLC configuration pages.
CommissioningThe module is ready for operation after connection of the supply voltage. The MODE button is available on the module panel to display the currently set IP address of the Ethernet interface. Parameters of all interfaces are set in the Mosaic programming environment. The exact setup procedure is given in the TXV 004 50 documentation.
Module diagnosticsThe basic diagnostic system of the module is part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled on the module display and are available for processing by the master system. For more information, see TXV 004 50.
Maintenance
DescriptionThe module does not require any maintenance under general installation conditions.
NoticeBecause the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
GenerallyWarranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
NoticeYou must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.

CP-2080 LTE - CPU, 2x ETH, 4 DI, 6 RO, 2 DO, CIB, LCD

Під замовлення, 40 днів
Код: TXN 120 80.11NSLN
від 66 934 
Способи оплати
Післяплата
Нова Пошта, Самовивіз
Оплата на рахунок
IBAN UA383253650000002600101565149
Способи доставки
Нова Пошта — від 70 грн
Самовивіз
Умови повернення
Повернення товару впродовж 14 днів за домовленістю
Чат